FIRE ALARM PANEL
PROGRAM Fire Alarm Control Panel, Model: PE-FA480 is manufactured and tested in accordance with EN 54-2 : 1997 (which is equivalent to MS1745-2 : 2004) and also conformed to the local CIFS requirement.
These controls are housed in a signal red metal enclosure with a glazed panel in front for clear visibility of the control and indications. The benefits of this product, it is cost-saving, user friendly and it could fit into various brands of conventional detectors. This is applicable for all hospital, campus, schools, factories, commercial buildings and office buildings.
FEATURES & INDICATIONS
- Main and D/C on Indicator
- Buzzer Mute Switch
- Main Fail Indicator
- Buzzer resound
- Battery Fail Indicator
- Main on/off Switch
- Charter Fail Indicator
- Test Lamp Switch
- Bell Line Fail Indicator
- Test Zone Alarm, Fault and Isolate Switch
- Zone Fire, Fault and Isolate Indicators
- Test Battery Push Button Switch
- Evacuate Switch and Indicator
- Master Reset Push Button Switch
- Fire Station Isolate Switch and Indicator
- Pumpsets status
- Bell Isolate Switch and Indicator
- CO-2 Discharge Status Auxiliary Trip Isolate Switch and Indicator
No. of
Zones |
Model | Normal Size in mm(W x H x D) |
Mimic Size in mm(W x H x D) |
2 to 6 | PE/ FA 20 -60 | 510x535x 204 | S60x 1170×230 |
8 to 12 | PE / FA80 120 | 510x586x204 | 560x 1220×230 |
15 – 24 | PE/ FA 140 -240 | 610 X 775 X 204 | 610 X 1401 X 230 |
27 – 36 | PE/ FA 260 -360 | 610 X 1026 X 230 | 610 X 1534 X 230 |
39 – 48 | PE/ FA 380 -480 | 610 X 1162 X 230 | 610 X 1670 X 230 |
Power Supply Input | 240V AC 50Hz |
Operating System | 24V DC |
Charger | Automatic/Trickle Type |
Charging Rate | 300mA (Trickle) and 2.5A (Boost) |
End Of Line | 8K Ohms |
Auxiliary Output | 24V 1Amp |
CMS Output | N/O Contact |
STANDBY MODE | |
Master | 75mA |
Per zone (with detectors) | 5mA |
ALARM MODE | |
Master | 140mA |
Per Trigger Zone | 50mA |
Output Devices | 150mA |
Per Bell | 30mA |